2024年6月5日发(作者:)

DNB(SDN)设备网故障总表

代码

名称

描述

正常显示,所显示的数字均是DNB(SDN)模块的节点号

Normal operation. The numeric display indicates the

1747-SDN’s node address on the DeviceNet network.

控制器没有通过重复节点地址检查。选择的节点地址已经在

使用。

Controller has Failed Duplicate Note Address node

address selected is already in use.

在DNB(SDN)的扫描列表中存在非法的数据(错误设备的节点

号码交替闪烁)

Illegal data in scan list table (node number alternately flashes).

至少一个从站设备停止通讯(设备网设备停止通讯设备的节

点号码交替闪烁)

Slave device stopped communicating (node number alternately

flashes).

DNB(SDN)扫描列表中的设备ID与实际设备ID不匹配(设备

的节点号码交替闪烁)

Device key parameters do not match scan list table entry (node

number alternately flashes).

通讯数据过多

Data overrun on port detected.

扫描模块没有收到网络流量。已经超过10秒时间模块没有

收到网络流量。

No network traffic received by the scanner.10 seconds have

elapsed and no network traffic for the module or for any other

device have been received by the module.

没有直接的网络数据交换

No direct network traffic for module detected.

建议

None.

改变DNB(SDN)模块的节点号,因为你所设置的

DNB(SDN)模块的节点号在设备网中已经存在

Change the module channel address to another

available one. The node address you selected is

already in use on that channel.

重新配置DNB(SDN)的扫描列表,删除所有的非

法数据

Reconfigure the scan list table and remove any

illegal data.

检查从站设备和确认连接是否正确

Inspect the field devices and verify connections.

在扫描列表中出现错误的设备处输入正确的设

备ID (厂商,产品号和产品类型)

Enter a matching scan list device sure

that the device at the flashing node address

matches the desired key parameters (vendor,

product code, product type).

修改设置到有效的数据位置

Modify your configuration and check for invalid

data.

确定扫描列表正确。检查网络连接。

Verify scanlist is correctly configured to scan

slave DeviceNet network

connections.

有其它在线激活设备,初始信息,但没有本模块

信息。

are other active devices on the

network,initiating messages,but none of the

messages are for the module.

重新配置DNB(SDN)模块或从站设备

Either reconfigure the slave device,or change the

module’s scanlist to match the slave device.

检查在扫描列表中存在的设备工作是否正常

将该设备添加到设备网中,或者在扫描列表中

删除该设备

Add the device to the network, or delete the scan

list entry for that device.

确保你的DNB(SDN)已经正确的连接到设备网

上,检查网络电缆,检查通讯波特率

Make sure that your module is connected to a

valid network. Check for disconnected cables.

Verify baud rate.

使控制器在运行模式

Put the controller into RUN mode and enable the

RUN bit in the Module Command Array.

检查在模块命令数组中的错误值。

Check the FAULT value in the Module Command

Array.

检查DNB(SDN)的扫描列表确保设备的输入和输

出数据的大小是正确的.检查设备的配置.

Check scan list table entry for slave device to

make sure that input and output data lengths are

correct. Check slave device configuration.

检查DNB(SDN)扫描列表,检查从设备的配置,

重启从站设备

Check accuracy of scan list table entry. Check

slave device slave device

0 - 63

70

71

72

73

74

75

节点重复

Duplicate

Note

非法数据

Illegal

Scanlist Data

从站通讯超

Slave

Timeout

电气信息不

匹配

Electronic

Key

Mismatch

没有收到信

No Messages

Received

没有本模块

需要信息

No Message

For Scanner

从站数据大

小不匹配

Slave Data

Size

Mismatch

无此设备

No Such

Device

通讯错误

Transmit

Failure

在空闲模式

In ldle Mode

扫描模块错

Scanner

Faulted

片段错误

Fragmentatio

n Error

从站设备初

始信息错误

Slave Init

Error

76

77

设备返回到DNB(SDN)中的数据与DNB(SDN)扫描列表中的数

据预留空间不匹配(设备的节点号码交替闪烁)

Data size returned does not match scan lists entry (node number

alternately flashes).

DNB(SDN)无法找到在扫描列表中设置好的设备(设备的节点

号码交替闪烁)

Slave device in scan list table does not exist (node number

alternately flashes).

78

79

80

81

82

83

DNB(SDN)无法向设备网发送消息

Module has failed to transmit a message.

模块没有激活

Module is in IDLE mode.

扫描模块已经停止收发I/O数据。

The Scanner has stopped producing and consuming I/O

condition does not affect the scanner’s system or

messaging modes.

设备的返回信息有部分错误发生

Error detected in sequence of fragmented I/O messages from

device (node number alternately flashes).

DNB(SDN)和设备通讯时设备有错误的信息返回

Slave device is returning error responses when module attempts

to communicate with it (node number alternately flashes).

84

85

86

87

88

89

90

没有初始化

Not Yet

Initialized

接收存储器

溢出

Receive

Buffer

Overflow

设备挂起

Device Went

Idle

DNB(SDN)正在初始化

Module is initializing the DeviceNet channel.

运行中设备返回数据的大小和预期值不同

Run time data size returned from slave device is not the size

expected.

DNB(SDN)在运行模式时设备挂起

Device is producing idle state data while the scanner is in Run

Mode.

Available for allocation. Scanner has not yet been detected by

allocated master, or slave mode is enabled but scanner is not

allocated to a master.

不是故障,请重新给DNB(SDN)模块上电或者复位。

This is not an error. At power-up and reset, the module displays

all 14 segments of the node address and status display LEDs.

从站对扫描模块的初始数据响应错误,或扫描模块的配置表

对某一从站是非法的。

Slave device responded with an error to the initialization data

sent to it by the scanner; or the configuration table in the

scanner’s flash memory is not valid for a slave node.

用户在软件中禁止了DNB(SDN)

User has disabled communication port

无.当模块正确启动后此代码自动清除

None. This code clears itself once module

attempts to initialize all slave devices on the

channel.

检查设备的初始化程序和配置,给从站设备配

置一个小点的数据尺寸。

Check slave device installation and

ure the slave device for a

smaller data size.

检查设备的配置或从站设备的当前状态

Check device configuration/slave node status.

Monitor scanner to determine if error code clears

when master detects scanner. If error remains,

check scanner slave mode configuration.

None.

重新下载adr.

Try the ADR download again. If it still fails, try

clearing the ADR flash by downloading an empty

ADR configuration to the scanner and then try the

ADR configuration again.

重新配置模块。检查程序中的DNB(SDN)命令寄

存器中的禁止位是否为1

Reconfigure your module. Check the disable bit in

the Module Command Register.

检查设备网线的连接和所有设备是否连接正

确。检查出现错误的设备或其它引起故障的设

备和接口

Check DeviceNet connections and physical media

integrity. Check system for failed slave devices or

other possible sources of network interference.

给设备网线提供24V电源。确保已将24V工作

电源正确的传输到DNB(SDN)的通讯端口上

Provide network power. Make sure that module

drop cable is providing network power to module

comm. port.

无。在升级未完成前请不要停止升级,否则将

丢掉在模块中已存在的固化信息

None. Do not disconnect the module while

application FLASH is in progress. You will lose

any existing data in the module’s memory.

None.

刷新固件。咨询服务商或者更换模块

Service or replace your module.

重启,刷新固件。咨询服务商或者更换模块

Service or replace your module.

Cycle power to module. Download configuration

to module.

91

设备自动重

置错误

Auto Device

Replacement(

ADR)Error

网络禁止

Disabled

Network

总线中断

Bus Off

没有电源

No DeviceNet

Power

固件升级

Flash Update

固件损坏

Firmware

Corrupted

硬件错误

Hard Fault

DNB(SDN)通讯口检测到通讯网线中断,DNB(SDN)检测到通讯

错误

Bus-off condition detected on comm port. Module is detecting

communication errors.

92

DNB(SDN)检测到设备网线上没有24V直流工作电源

No network power detected on comm port.

95

97

98

99

E9

DNB(SDN)正在升级

Application FLASH update in progress.

在软件中将DNB(SDN)暂停使用

Module halted by user command.

不可恢复的故障

Unrecoverable firmware failure.

不可恢复的硬件故障

Unrecoverable hardware failure.

Non-volatile configuration corrupt